Quick Installation Guide
00825-0100-4697, Rev DB
September 2011
Rosemount 848T
9
NOTE
To make changes to the AI block, the BLOCK_MODE (TARGET) must be set to OOS (out of
service). Once the changes are made, return the BLOCK_MODE TARGET to AUTO.
Multiple Analog Input (MAI) Function Block
The MAI block processes up to eight field device measurements and makes the output
available to other function blocks. The output value of the MAI block is in engineering units
and contains a status indicating the quality of the measurements. Use the Channel number
to define the variables that the MAI block processes. At a minimum, verify the parameters of
the MAI block in Table 3.
NOTE
To make changes to the MAI block, the BLOCK_MODE (TARGET) must be set to OOS (out
of service). Once the changes are made, return the BLOCK_MODE TARGET to AUTO.
Table 2. AI Block Parameters
(1)
(1) Configure one AI Block for each desired measurement.
Parameter Comments
CHANNEL Choices:
1. Sensor 1 – 8
2. Differential Sensors 1 – 4
3. Body Temperature
L_TYPE For most measurements, set to “DIRECT”
XD_SCALE Set the desired measurement range and units. Units
must be one of the following:
•mV
•Ohms
•°C
•°F
•°R
•K
OUT_SCALE For “DIRECT” L_TYPE, set OUT_SCALE to match
XD_SCALE
HI_HI_LIM
LO_LO_LIM
HI_LIM
LO_LIM
Process alarms.
Must be within the range defined by “OUT_SCALE”
Table 3. MAI Block Parameters
Parameter Comments
CHANNEL Choices:
1. Channels 1 – 8
2. Custom Settings (see Rosemount 848T reference manual for
more information).
L_TYPE For most measurements, set to “DIRECT”
XD_SCALE Set desired measurement range and units. Units must be one of
the following:
•mV
•Ohms
•°C
•°F
•°R
•K
OUT_SCALE For “DIRECT” L_TYPE, set OUT_SCALE to match XD_SCALE