Quick Installation Guide
00825-0100-4697, Rev DB
September 2011
Rosemount 848T
5
STEP 2 CONTINUED...
Sensor Wiring and Power Supply
Compatible with eight independently configurable channels including combinations of 2-
and 3-wire RTDs, thermocouples, mV, ohm and mA sensors.
All sensor and power terminals are rated to 42.4 Vdc.
•F
OUNDATION fieldbus network powered with a terminal voltage of 9.0 to 32.0 Vdc and 22
mA maximum current draw.
For best network performance twisted, shielded pair cabling should be used. Proper
gage wire should be selected to maintain the 9.0 Vdc minimum.
Figure 7. Sensor Wiring Diagram
The wiring of 3-wire RTDs for this unit is different than some earlier 848T models. Pay
careful attention to the wiring diagram on the label, especially if this unit is replacing an older
unit.
Wiring Analog Inputs
Figure 8. 848T Analog Input Wiring Diagram9
* Emerson Process Management provides 4-wire sensors for all single-element RTDs. Use
these RTDs in 3-wire configurations by clipping the fourth lead or leaving it disconnected and
insulated with electrical tape.
** The transmitter must be configured for a 3-wire RTD in order to recognize an RTD with a
compensation loop.
123
2-wire
RTD and
Ohms
3-wire
RTD and
Ohms*
Thermocouples /
Ohms and
Millivolts
123 123
2-Wire RTD
with
Compensation
Loop**
123
Analog Input Connectors
Power Supply
Analog Transmitters