Quick Installation Guide
00825-0100-4697, Rev DB
September 2011
Rosemount 848T
6
Typical Configuration for FOUNDATION fieldbus Networking
NOTE
Each segment in a F
OUNDATION fieldbus trunk must be terminated at both ends.
Ground the Transmitter
Proper ground is crucial to reliable temperature readings.
Ungrounded Thermocouple, mV, and RTD/Ohm Inputs
Option 1:
1. Connect F
OUNDATION fieldbus signal wiring shield to the sensor wiring shield(s).
2. Ensure the shields are tied together and electrically isolated from the transmitter enclosure.
3. Only ground the shield at the power supply end.
4. Ensure that the sensor shield(s) is electrically isolated from the surrounding
grounded fixtures.
Power
Supply
Terminators
Integrated Power
Conditioner and Filter
(Spur)
(Spur)
FOUNDATION
™
fieldbus Host or
configuration tool
6234 ft (1900 m) max
(Trunk)
Signal Wiring
(depending upon cable characteristics)
Sensor Wires
Power
Supply
Shield ground point
848T